  •  (1) Except as provided in section 17, all electrical equipment and facilities located out-of-doors within 25 feet of a storage tank, loading, unloading rack or terminal, pump or pumphouse used for Class I flammable liquids or crude petroleum shall comply with the requirements of the Canadian Electrical Code for Class I, Division II, Group D hazardous locations.

  • (2) Except as provided in section 41, all electrical equipment and facilities located inside a pumphouse, warehouse or other building where any flammable liquid is dispensed, processed or otherwise exposed to evaporation, leakage or spillage, or where Class I flammable liquids are stored or handled shall comply with the requirements of the Canadian Electrical Code for Class I, Division I, Group D hazardous locations.

  • (3) All electrical equipment and facilities used in environments where explosion proof equipment and facilities are prescribed in this section shall be approved for Class I, Division I, Group D hazardous locations and shall be so marked or labelled by the manufacturer.