Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations (SOR/2008-197)
Full Document:
- HTMLFull Document: Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations (Accessibility Buttons available) |
- XMLFull Document: Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations [144 KB] |
- PDFFull Document: Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations [355 KB]
Regulations are current to 2026-09-30 and last amended on 2025-08-28. Previous Versions
21 The tank precision leak detection test referred to in section 16 and paragraphs 19(1)(c), 26(a) and 43(b) must
(a) be capable of measuring the level of water in the tank to within 3 mm with a probability of 0.95 or greater;
(b) if a volumetric method is used, be capable of measuring the level of liquid in the tank to within 3 mm with a probability of 0.99 or greater;
(c) be capable of detecting a leak rate of at least 0.38 L/h within a 24 hour period with a probability of detection of 0.95 or greater and a probability of false alarm of 0.05 or less, accounting for variables such as vapour pockets, thermal expansion and contraction, evaporation and condensation, temperature stratification, groundwater level and tank deformation; and
(d) be performed, using a documented and validated method, by an individual trained in the maintenance and use of the test equipment.
Page Details
- Date modified: