  1. Flammable Liquids Bulk Storage Regulations - C.R.C., c. 1148 (Section 3)
    Regulations Respecting the Design, Location, Construction, Operation and Maintenance of Stationary Bulk Storage Facilities for Flammable Liquids

     These Regulations apply to the stationary bulk storage facilities for flammable liquids located on the right-of-way owned or leased by any railway company subject to the jurisdiction of the Canadian Transport Commission; facilities previously approved by an order of the Commission shall be operated and maintained in accordance with these Regulations and, unless otherwise ordered by the Commission, need not conform to those parts of these Regulations pertaining to location, construction and design.


  2. Flammable Liquids Bulk Storage Regulations - C.R.C., c. 1148 (Section 60)
    Regulations Respecting the Design, Location, Construction, Operation and Maintenance of Stationary Bulk Storage Facilities for Flammable Liquids

     No electric lines other than those serving the installation shall cross over the installation. These lines shall not be constructed over tanks and shall be restricted to non-hazardous areas.


  3. Flammable Liquids Bulk Storage Regulations - C.R.C., c. 1148 (Section 57)
    Regulations Respecting the Design, Location, Construction, Operation and Maintenance of Stationary Bulk Storage Facilities for Flammable Liquids
    • [...]

    • (4) Dikes for crude petroleum shall have a net capacity not less than the capacity of all the storage tanks in the diked area. The dikes shall be provided with flareback sections at the top of the dike designed to turn back a boil-over wave. These flareback sections shall not be required for dikes enclosing approved floating roof storage tanks, or when storage tanks are provided with approved attached extinguishing systems.


  4. Flammable Liquids Bulk Storage Regulations - C.R.C., c. 1148 (Section 4)
    Regulations Respecting the Design, Location, Construction, Operation and Maintenance of Stationary Bulk Storage Facilities for Flammable Liquids

     These Regulations do not apply to a “company”, as defined in section 2 of the National Energy Board Act.


  5. Flammable Liquids Bulk Storage Regulations - C.R.C., c. 1148 (Section 1)
    Regulations Respecting the Design, Location, Construction, Operation and Maintenance of Stationary Bulk Storage Facilities for Flammable Liquids

     These Regulations may be cited as the Flammable Liquids Bulk Storage Regulations.



Date modified: