Hull Construction Regulations
185 (1) Subject to subsection (2), no duct provided for the ventilation of an accommodation space, service space or control station shall pass through a machinery space of Category A or galley unless the duct is
(a) constructed of steel in accordance with the requirements of subsection 184(1);
(b) suitably supported and stiffened; and
(c) fitted close to every boundary penetrated with a fire damper that is
(i) of the fail-safe automatic closing type, and
(ii) capable of being manually operated from either side of the division.
(2) A duct provided for the ventilation of an accommodation space, service space or control station may pass through a machinery space of Category A or galley if the duct is
(a) constructed of steel; and
(b) insulated to an ‘A-60’ Class fire rating where it passes through the machinery space or galley.
- SOR/83-521, s. 4