Hull Construction Regulations

Version of section 186 from 2006-03-22 to 2017-02-02:


 Where an exhaust duct from a galley range passes through an accommodation space or space containing combustible materials, the duct shall be insulated to an ‘A’ Class fire rating and shall be fitted with

  • (a) a grease trap that is readily removable for cleaning;

  • (b) a fire damper located in the lower end of the duct;

  • (c) a device, operable from within the galley, for shutting off the exhaust fan; and

  • (d) a fixed means for extinguishing a fire within the duct.

  • SOR/83-521, s. 4