Government of Canada / Gouvernement du Canada
Symbol of the Government of Canada

Search

Energy Efficiency Regulations, 2016

Version of section 118 from 2016-12-09 to 2017-06-27:

The following provision is not in force.

Marginal note:Energy efficiency standards — cooled by air

  •  (1) The energy efficiency standards set out in column 3 of Table 1 to this section apply to large air conditioners that are cooled by air and described in column 1 and that are manufactured during the period set out in column 4.

  • Marginal note:Energy efficiency standards — cooled by water or evaporation

    (2) The energy efficiency standards set out in column 3 of Table 2 to this section apply to large air conditioners that are cooled by water or evaporation and described in column 1 and that are manufactured during the period set out in column 4.

  • Marginal note:Testing standard

    (3) A large air conditioner complies with the energy efficiency standard set out in column 3 if it meets that standard when tested in accordance with testing procedures established by the standard set out in column 2 that are applicable to a large air conditioner as defined in section 116.

    TABLE 1

    Column 1Column 2Column 3Column 4
    ItemEnergy-using ProductStandardEnergy Efficiency StandardPeriod of Manufacture
    1Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and either without a heating section or with an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 10.3On or after December 31, 1998 and before January 1, 2010
    2Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and either without a heating section or with an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.2

    IEER ≥ 11.4

    On or after January 1, 2010
    3Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and either without a heating section or with an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 9.7On or after December 31, 1998 and before January 1, 2010
    4Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and either without a heating section or with an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.0

    IEER ≥ 11.2

    On or after January 1, 2010
    5Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and either without a heating section or with an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 10.0

    IEER ≥ 10.1

    On or after January 1, 2010
    6Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and a heating section other than an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 10.1On or after December 31, 1998 and before January 1, 2010
    7Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and a heating section other than an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.0

    IEER ≥ 11.2

    On or after January 1, 2010
    8Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and a heating section other than an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 9.5On or after December 31, 1998 and before January 1, 2010
    9Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and a heating section other than an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 10.8

    IEER ≥ 11.0

    On or after January 1, 2010
    10Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and a heating section other than an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 9.8

    IEER ≥ 9.9

    On or after January 1, 2010

    TABLE 2

    Column 1Column 2Column 3Column 4
    ItemEnergy-using ProductStandardEnergy Efficiency StandardPeriod of Manufacture
    1Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and either without a heating section or with an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 11.5On or after December 31, 1998 and before January 1, 2010
    2Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and either without a heating section or with an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.5

    IEER ≥ 11.7

    On or after January 1, 2010
    3Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and either without a heating section or with an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 11.0On or after December 31, 1998 and before January 1, 2010
    4Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and either without a heating section or with an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.0

    IEER ≥ 11.2

    On or after January 1, 2010
    5Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and a heating section other than an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 11.3On or after December 31, 1998 and before January 1, 2010
    6Large air conditioners that have a cooling capacity of ≥ 19 kW and < 40 kW and a heating section other than an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.3

    IEER ≥ 11.5

    On or after January 1, 2010
    7Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and a heating section other than an electric heating sectionCSA C746-98Energy efficiency ratio ≥ 10.8On or after December 31, 1998 and before January 1, 2010
    8Large air conditioners that have a cooling capacity of ≥ 40 kW and < 70 kW and a heating section other than an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 10.8

    IEER ≥ 11.0

    On or after January 1, 2010
    9Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and either no heating section or with an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 11.0

    IEER ≥ 11.1

    On or after January 1, 2010
    10Large air conditioners that have a cooling capacity of ≥ 70 kW and < 223 kW and a heating section other than an electric heating section

    CSA C746-06 for energy efficiency ratio

    AHRI 340/360 for IEER

    Energy efficiency ratio ≥ 10.8

    IEER ≥ 10.9

    On or after January 1, 2010

Date modified: