Government of Canada / Gouvernement du Canada
Symbol of the Government of Canada

Search

Energy Efficiency Regulations, 2016

Version of section 657 from 2019-04-30 to 2019-12-11:


Marginal note:Definitions

 The following definitions apply in this Subdivision.

annual walk-in energy factor

annual walk-in energy factor means the ratio of total heat removed from an enclosed space, excluding heat generated by the operation of the walk-in refrigeration system, to the total energy input of the walk-in refrigeration system during a one-year period, expressed in watt-hours per watt-hours. (facteur énergétique annuel de la chambre froide)

dedicated condensing unit

dedicated condensing unit means a positive displacement condensing unit that

  • (a) is part of a refrigeration system, including a matched refrigeration system;

  • (b) has one or more compressors, one condenser and one refrigeration circuit; and

  • (c) is designed to serve one refrigerated load. (unité de condensation dédiée)

display door assembly

display door assembly means a walk-in door assembly that is designed for product display and that has 75% or more of its surface area composed of glass or other transparent material. (assemblage de porte de présentation)

floor panel

floor panel means a walk-in panel that is installed, or designed to be installed, as the floor of a walk-in freezer. (panneau de plancher)

freight door assembly

freight door assembly means a walk-in door assembly, other than a display door assembly, that is 1.22 m (4 feet) or more in width and 2.44 m (8 feet) or more in height. (assemblage de porte de quai de chargement)

passage door assembly

passage door assembly means a walk-in door assembly that is not a display door assembly or a freight door assembly. (assemblage de porte de passage)

R-value

R-value means, in respect of a walk-in panel and a walk-in door assembly, its thermal resistance, expressed in square metre kelvins per watt. (valeur-R)

single-package dedicated system

single-package dedicated system means a single-package refrigeration system that has

  • (a) one or more compressors, one condenser and a means of forced circulation of refrigerated air; and

  • (b) components by which heat is transferred from air to refrigerant without any components that are external to the system imposing resistance to the flow of the refrigerated air. (système dédié monobloc)

structural panel

structural panel means a walk-in panel that is installed, or is designed to be installed, as the ceiling or a wall of a walk-in cooler or walk-in freezer. (panneau de structure)

10 C.F.R. Appendix A

10 C.F.R. Appendix A means Appendix A to Subpart R, Part 431 of Title 10 to the United States Code of Federal Regulations, entitled Uniform Test Method for the Measurement of Energy Consumption of the Components of Envelopes of Walk-In Coolers and Walk-In Freezers, as amended from time to time. (appendice A 10 C.F.R.)

10 C.F.R. Appendix B

10 C.F.R. Appendix B means Appendix B to Subpart R, Part 431 of Title 10 to the United States Code of Federal Regulations, entitled Uniform Test Method for the Measurement of R-Value for Envelope Components of Walk-In Coolers and Walk-In Freezers, as amended from time to time. (appendice B 10 C.F.R.)

10 C.F.R. Appendix C

10 C.F.R. Appendix C means Appendix C to Subpart R, Part 431 of Title 10 to the United States Code of Federal Regulations, entitled Uniform Test Method for the Measurement of Net Capacity and AWEF of Walk-In Cooler and Walk-In Freezer Refrigeration Systems, as amended from time to time. (appendice C 10 C.F.R.)

10 C.F.R. §431.304

10 C.F.R. §431.304 means section 431.304 of Subpart R, Part 431 of Title 10 to the United States Code of Federal Regulations, as amended from time to time. (10 C.F.R. §431.304)

walk-in cooler

walk-in cooler means an enclosed storage space that has an area of less than 278.71 m2 (3,000 square feet) and is designed to be cooled to temperatures at or above 0° C and to allow a person to enter. (réfrigérateur-chambre)

walk-in door assembly

walk-in door assembly means an assembly that

  • (a) is installed, or is designed to be installed, in an opening of an interior or exterior wall of a walk-in cooler or walk-in freezer in order to allow access through the opening or to close it off; and

  • (b) consists of the framing material necessary for its attachment and a moveable door panel, including any glass, door plugs or mullions. (assemblage de porte de chambre froide)

walk-in freezer

walk-in freezer means an enclosed storage space that has an area of less than 278.71 m2 (3000 square feet) and is designed to be cooled to temperatures below 0° C and to allow a person to enter. (congélateur-chambre)

walk-in panel

walk-in panel means a panel that is installed, or is designed to be installed, as part of the envelope of a walk-in cooler or walk-in freezer. It does not include a walk-in door assembly. (panneau de chambre froide)

walk-in process cooling refrigeration system

walk-in process cooling refrigeration system means a refrigeration system that

  • (a) is sold as a set with an insulated enclosure and, when assembled with the enclosure, has a cooling capacity of at least 1.035 kW/m3 (100 Btu/h/ft3) of enclosed internal volume;

  • (b) is sold as a set that has a dedicated condensing unit and an assembly that has a means of forced air circulation and an evaporator coil that has a height that is

    • (i) at least 1.37 m (4.5 feet), as measured perpendicular to the tubes, and

    • (ii) at least one-and-a half times the width, as measured parallel to the tubes; or

  • (c) is sold as a set that has a dedicated condensing unit and an evaporator coil. (système de réfrigération de type chambre pour refroidissement industriel)

walk-in refrigeration system

walk-in refrigeration system means a refrigeration system that is installed, or is designed to be installed, in a walk-in cooler for the purpose of cooling its refrigerated compartment and has a dedicated condensing unit or a single-package dedicated system. It includes all controls and other components that are integral to its operation but does not include a walk-in process cooling refrigeration system. (système de réfrigération de chambre froide)

  • SOR/2018-201, s. 76

Date modified: