Energy Efficiency Regulations, 2016
Version of section 130 from 2017-06-28 to 2019-12-11:
Marginal note:Energy efficiency standards
130 (1) The energy efficiency standards set out in column 2 of the table to this section apply to single package vertical air conditioners described in column 1 that are manufactured on or after January 1, 2011.
Marginal note:Testing standard
(2) A single package vertical air conditioner complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by CSA C746-06 that are applicable to a single package vertical air conditioner as defined in section 128.
Column 1 Column 2 Item Energy-using Product Energy Efficiency Standard 1 Single package vertical air conditioners that have a cooling capacity of < 19 kW (65,000 Btu/h) Energy efficiency ratio ≥ 9.0 2 Single package vertical air conditioners that have a cooling capacity of ≥ 19 kW (65,000 Btu/h) and < 39.5 kW (135,000 Btu/h) Energy efficiency ratio ≥ 8.9 3 Single package vertical air conditioners that have a cooling capacity of ≥ 39.5 kW (135,000 Btu/h) Energy efficiency ratio ≥ 8.6
- Date modified: