Government of Canada / Gouvernement du Canada
Symbol of the Government of Canada

Search

Energy Efficiency Regulations, 2016

Version of section 317 from 2023-06-21 to 2024-08-18:


Marginal note:Energy efficiency standards — household

  •  (1) The energy efficiency standards set out in column 3 of Table 1 to this section apply to household gas boilers described in column 1 that are manufactured during the periods set out in column 4.

  • Marginal note:Testing standard — household

    (2) A household gas boiler complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by the standard set out in column 2 of Table 1 that are applicable to a gas boiler as defined in section 315.

  • Marginal note:Energy efficiency standards — commercial

    (3) The energy efficiency standards set out in column 2 of Table 2 to this section apply to commercial gas boilers described in column 1 that are manufactured on or after January 1, 2025.

  • Marginal note:Testing standard — commercial

    (4) A commercial gas boiler complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by 10 C.F.R. Appendix A that are applicable to a gas boiler as defined in section 315.

    TABLE 1

    ItemColumn 1Column 2Column 3Column 4
    Energy-using ProductTesting StandardEnergy Efficiency StandardPeriod of Manufacture
    1Household gas boilers that are intended for low pressure steam systemsCGA P.2Annual fuel utilization efficiency ≥ 75%On or after December 31, 1998 and before September 1, 2010
    2Household gas boilers that are intended for low pressure steam systemsCSA P.2 for annual fuel utilization efficiency

    Annual fuel utilization efficiency ≥ 80%

    No continuously burning pilot light

    On or after September 1, 2010 and before January 15, 2021
    2.1Household gas boilers that are intended for low pressure steam systemsCSA P.2 for annual fuel utilization efficiency, standby power and off-mode power

    Annual fuel utilization efficiency ≥ 82%

    No continuously burning pilot light

    Standby power ≤ 8 W

    Off-mode power ≤ 8 W

    On or after January 15, 2021
    3Household gas boilers that are intended for hot water systemsCGA P.2Annual fuel utilization efficiency ≥ 80%On or after December 31, 1998 and before September 1, 2010
    4Household gas boilers that are intended for hot water systemsCSA P.2 for annual fuel utilization efficiency

    Annual fuel utilization efficiency ≥ 82%

    No continuously burning pilot light

    On or after September 1, 2010 and before September 1, 2012
    5Household gas boilers that are intended for hot water systems and have tankless domestic water heating coilsCSA P.2 for annual fuel utilization efficiency

    Annual fuel utilization efficiency ≥ 82%

    No continuously burning pilot light

    On or after September 1, 2012 and before July 1, 2023
    5.1Household gas boilers that are intended for hot water systems and have tankless domestic water heating coilsCSA P.2 for annual fuel utilization efficiency, standby power and off-mode power

    Annual fuel utilization efficiency ≥ 90%

    No continuously burning pilot light

    Standby power ≤ 9 W

    Off-mode power ≤ 9 W

    On or after July 1, 2023
    6Household gas boilers that are intended for hot water systems and do not have tankless domestic water heating coilsCSA P.2 for annual fuel utilization efficiency

    Annual fuel utilization efficiency ≥ 82%

    No continuously burning pilot light

    Equipped with automatic water temperature adjustment device and not operable without the device

    On or after September 1, 2012 and before July 1, 2023
    7Household gas boilers that are intended for hot water systems and do not have tankless domestic water heating coilsCSA P.2 for annual fuel utilization efficiency, standby power and off-mode power

    Annual fuel utilization efficiency ≥ 90%

    No continuously burning pilot light

    Equipped with automatic water temperature adjustment device and not operable without the device

    Standby power ≤ 9 W

    Off-mode power ≤ 9 W

    On or after July 1, 2023

    TABLE 2

    ItemColumn 1Column 2
    Energy-using ProductEnergy Efficiency Standard
    1Commercial gas boilers that have an input rate of ≥ 87.92 kW (300,000 Btu/h) but ≤ 732.68 kW (2,500,000 Btu/h) and are intended for hot water systemsThermal efficiency ≥ 90%
    2Commercial gas boilers that have an input rate of > 732.68 kW (2,500,000 Btu/h) but ≤ 2 930.71 kW (10,000,000 Btu/h) and are intended for hot water systemsCombustion efficiency ≥ 90%
    3Commercial gas boilers that have an input rate of ≥ 87.92 kW (300,000 Btu/h) but ≤ 732.68 kW (2,500,000 Btu/h) and are intended for low pressure steam systemsThermal efficiency ≥ 81%
    4Commercial gas boilers that have an input rate of > 732.68 kW (2,500,000 Btu/h) but ≤ 2 930.71 kW (10,000,000 Btu/h) and are intended for low pressure steam systemsThermal efficiency ≥ 82%
  • SOR/2019-164, s. 17
  • SOR/2022-265, s. 47

Date modified: