Government of Canada / Gouvernement du Canada
Symbol of the Government of Canada

Search

Energy Efficiency Regulations, 2016

Version of section 321 from 2019-12-12 to 2023-06-20:


Marginal note:Energy efficiency standards — household

  •  (1) The energy efficiency standards set out in column 3 of Table 1 to this section apply to household oil-fired boilers described in column 1 that are manufactured during the periods set out in column 4.

  • Marginal note:Testing standard — household

    (2) A household oil-fired boiler complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by the standard set out in column 2 of Table 1 that are applicable to an oil-fired boiler as defined in section 319.

  • Marginal note:Energy-efficiency standards — commercial

    (3) The energy efficiency standards set out in column 2 of Table 2 to this section apply to commercial oil-fired boilers described in column 1 that are manufactured on or after January 1, 2025.

  • Marginal note:Testing Standard — commercial

    (4) A commercial oil-fired boiler complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by 10 C.F.R. Appendix A that are applicable to an oil-fired boiler as defined in section 319.

    TABLE 1

    ItemColumn 1Column 2Column 3Column 4
    Energy-using ProductStandardEnergy Efficiency StandardPeriod of Manufacture
    1Household oil-fired boilersCSA B212Seasonal energy utilization efficiency ≥ 80%On or after December 31, 1998 and before September 1, 2010
    2Household oil-fired boilers that are intended for low pressure steam systemsASHRAE 103Annual fuel utilization efficiency ≥ 82%On or after September 1, 2010 and before January 15, 2021
    2.1Household oil-fired boilers that are intended for low pressure steam systemsCSA P.2 for annual fuel utilization efficiency, standby power and off-mode power

    Annual fuel utilization efficiency ≥ 85%

    Standby power ≤ 11 W

    Off-mode power ≤ 11 W

    On or after January 15, 2021
    3Household oil-fired boilers that are intended for hot water systemsASHRAE 103Annual fuel utilization efficiency ≥ 84%On or after September 1, 2010 and before September 1, 2012
    4Household oil-fired boilers that are intended for hot water systems and have tankless domestic water heating coilsASHRAE 103Annual fuel utilization efficiency ≥ 84%On or after September 1, 2012 and before January 15, 2021
    4.1Household oil-fired boilers that are intended for hot water systems and have tankless domestic water heating coilsCSA P.2 for annual fuel utilization efficiency, standby power and off-mode power

    Annual fuel utilization efficiency ≥ 86%

    Standby power ≤ 11 W

    Off-mode power ≤ 11 W

    On or after January 15, 2021
    5Household oil-fired boilers that are intended for hot water systems and do not have tankless domestic water heating coilsASHRAE 103 for annual fuel utilization efficiency

    Annual fuel utilization efficiency‍ ≥ 84%

    Equipped with automatic water temperature adjustment device and not operable without the device

    On or after September 1, 2012 and before January 15, 2021
    6Household oil-fired boilers that are intended for hot water systems and do not have tankless domestic water heating coilsCSA P.2 for annual fuel utilization efficiency, standby power and off-mode power

    Annual fuel utilization efficiency ≥ 86%

    Equipped with automatic water temperature adjustment device and not operable without the device

    Standby power ≤ 11 W

    Off-mode power ≤ 11 W

    On or after January 15, 2021

    TABLE 2

    ItemColumn 1Column 2
    Energy-using ProductEnergy Efficiency Standard
    1Commercial oil-fired boilers that have an input rate of ≥ 87.92 kW (300,000 Btu/h) but ≤ 732.68 kW (2,500,000 Btu/h) and are intended for hot water systemsThermal efficiency ≥ 87%
    2Commercial oil-fired boilers that have an input rate of > 732.68 kW (2,500,000 Btu/h) but ≤ 2 930.71 kW (10,000,000 Btu/h) and are intended for hot water systemsCombustion efficiency ≥ 88%
    3Commercial oil-fired boilers that have an input rate of ≥ 87.92 kW (300,000 Btu/h) but ≤ 732.68 kW (2,500,000 Btu/h) and are intended for low pressure steam systemsThermal efficiency ≥ 84%
    4Commercial oil-fired boilers that have an input rate of > 732.68 kW (2,500,000 Btu/h) but ≤ 2 930.71 kW (10,000,000 Btu/h) and are intended for low pressure steam systemsThermal efficiency ≥ 85%
  • SOR/2019-164, s. 22