Government of Canada / Gouvernement du Canada
Symbol of the Government of Canada

Search

Energy Efficiency Regulations, 2016

Version of section 209 from 2019-12-12 to 2024-11-26:


Marginal note:Energy efficiency standards

  •  (1) The energy efficiency standards set out in column 2 of the table to this section apply to single package vertical heat pumps described in column 1 that are manufactured during the periods set out in column 3.

  • Marginal note:Testing standard

    (2) A single package vertical heat pump complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by CSA C746-17 that are applicable to a single package vertical heat pump as defined in section 207.

    TABLE

    ItemColumn 1Column 2Column 3
    Energy-using ProductEnergy Efficiency StandardPeriod of manufacture
    1Single package vertical heat pumps that have a cooling capacity of < 19 kW (65,000 Btu/h)

    Energy efficiency ratio ≥ 9.0

    Heating coefficient of performance ≥ 3.0

    On or after January 1, 2011 and before September 23, 2019
    2Single package vertical heat pumps that have a cooling capacity of < 19 kW (65,000 Btu/h)

    Energy efficiency ratio ≥ 11.0

    Heating coefficient of performance ≥ 3.3

    On or after September 23, 2019
    3Single package vertical heat pumps that have a cooling capacity of ≥ 19 kW (65,000 Btu/h) and < 39.5 kW (135,000 Btu/h)

    Energy efficiency ratio ≥ 8.9

    Heating coefficient of performance ≥ 3.0

    On or after January 1, 2011 and before October 9, 2015
    4Single package vertical heat pumps that have a cooling capacity of ≥ 19 kW (65,000 Btu/h) and < 39.5 kW (135,000 Btu/h

    Energy efficiency ratio ≥ 10.0

    Heating coefficient of performance ≥ 3.0

    On or after October 9, 2015
    5Single package vertical heat pumps that have a cooling capacity of ≥ 39.5 kW (135,000 Btu/h) and < 70 kW (240,000 Btu/h)

    Energy efficiency ratio ≥ 8.6

    Heating coefficient of performance ≥ 2.9

    On or after January 1, 2011 and before October 9, 2016
    6Single package vertical heat pumps that have a cooling capacity of ≥ 39.5 kW (135,000 Btu/h) and < 70 kW (240,000 Btu/h)

    Energy efficiency ratio ≥ 10.0

    Heating coefficient of performance ≥ 3.0

    On or after October 9, 2016
  • SOR/2019-163, s. 39

Date modified: