Energy Efficiency Regulations, 2016
Marginal note:Energy efficiency standards
209 (1) The energy efficiency standards set out in column 2 of the table to this section apply to single package vertical heat pumps described in column 1 that are manufactured on or after January 1, 2011.
Marginal note:Testing standard
(2) A single package vertical heat pump complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by CSA C746-06 that are applicable to a single package vertical heat pump as defined in section 207.
Column 1 Column 2 Item Energy-using Product Energy Efficiency Standard 1 Single package vertical heat pumps that have a cooling capacity of < 19 kW (65,000 Btu/h) Energy efficiency ratio ≥ 9.0
Heating coefficient of performance ≥ 3.0
2 Single package vertical heat pumps that have a cooling capacity of ≥ 19 kW (65,000 Btu/h) and < 39.5 kW (135,000 Btu/h) Energy efficiency ratio ≥ 8.9
Heating coefficient of performance ≥ 3.0
3 Single package vertical heat pumps that have a cooling capacity of ≥ 39.5 kW (135,000 Btu/h) Energy efficiency ratio ≥ 8.6
Heating coefficient of performance ≥ 2.9