Energy Efficiency Regulations, 2016

Version of section 666 from 2019-04-30 to 2019-12-11:


Marginal note:Energy efficiency standards

  •  (1) The following energy efficiency standards apply to a walk-in refrigeration system that is manufactured on or after January 1, 2020:

    • (a) if its condenser is designed and marketed only for use indoors, the product must have an annual walk-in energy factor of 1.644 or more;

    • (b) if its condenser is designed and marketed only for use outdoors, the product must have an annual walk-in energy factor of 2.227 or more; and

    • (c) if its condenser is designed and marketed for use both indoors and outdoors, the product must meet the energy efficiency standards set out in paragraphs (a) and (b).

  • Marginal note:Testing standard

    (2) A walk-in refrigeration system complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by 10 C.F.R. Appendix C that are applicable to a walk-in refrigeration system as defined in section 657.

  • SOR/2018-201, s. 76