Energy Efficiency Regulations, 2016
Version of section 666 from 2019-12-12 to 2023-06-20:
Marginal note:Energy efficiency standards
666 (1) The energy efficiency standards set out in column 2 of the table to this section apply to walk-in refrigeration systems described in column 1 that are manufactured during the periods set out in column 3.
Marginal note:Testing standard
(2) A walk-in refrigeration system complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by 10 C.F.R. Appendix C that are applicable to a walk-in refrigeration system as defined in section 657.
Item Column 1 Column 2 Column 3 Energy-using Product Energy Efficiency Standard Period of Manufacture 1 Walk-in cooler dedicated condensing refrigeration systems for use indoors Annual walk-in energy factor ≥ 1.644 On or after January 1, 2020 2 Walk-in cooler dedicated condensing refrigeration systems for use outdoors Annual walk-in energy factor ≥ 2.227 On or after January 1, 2020 3 Walk-in freezer dedicated condensing refrigeration systems for use indoors with a net refrigeration capacity of < 1900 W (6,500 Btu/h) Annual walk-in energy factor ≥ 9.091 x 10-5 x qnet + 0.530 On or after July 10, 2020 4 Walk-in freezer dedicated condensing refrigeration systems for use indoors with a net refrigeration capacity of ≥ 1900 W (6,500 Btu/h) Annual walk-in energy factor ≥ 0.703 On or after July 10, 2020 5 Walk-in freezer dedicated condensing refrigeration system for use outdoors with a net refrigeration capacity of < 1900 W (6,500 Btu/h) Annual walk-in energy factor ≥ 6.522 x 10-5 x qnet + 0.800 On or after July 10, 2020 6 Walk-in freezer dedicated condensing refrigeration systems for use outdoors with a net refrigeration capacity of ≥ 1900 W (6,500 Btu/h) Annual walk-in energy factor ≥ 0.923 On or after July 10, 2020 7 Walk-in cooler unit coolers with a fan motor that operates using direct current or has a nominal voltage of not more than 480 V AC Annual walk-in energy factor ≥ 2.638 On or after July 10, 2020 8 Walk-in freezer unit coolers with a net refrigeration capacity of < 4540 W (15,500 Btu/h) Annual walk-in energy factor ≥ 1.575x 10-5 x qnet + 1.146 On or after July 10, 2020 9 Walk-in freezer unit coolers with a net refrigeration capacity of ≥ 4540 W(15,500 Btu/h Annual walk-in energy factor ≥ 1.216 On or after July 10, 2020
- SOR/2018-201, s. 76
- SOR/2019-163, s. 52
- Date modified: