Explosives Regulations, 2013
Marginal note:Storage requirements — dwelling
288 (1) When propellant powder or percussion caps are stored in a dwelling, they must be stored away from flammable substances and sources of ignition. People not authorized by the retailer must not be given unlimited access to the propellant powder or percussion caps.
Marginal note:Storage requirements — storage unit
(2) When propellant powder or percussion caps are stored in a storage unit,
(a) the storage unit must be located in a dry place, away from flammable substances and sources of ignition;
(b) the storage unit must be constructed and maintained to prevent unauthorized access and to protect the contents from weather;
(c) if the storage unit is a container, it must not impede exit in case of fire;
(d) if the storage unit is not a container, all exits must be kept unobstructed;
(e) any shelving in the storage unit must be made from a non-sparking material (for example, wood or painted metal);
(f) nothing other than small arms cartridges may be stored with the propellant powder or percussion caps;
(g) propellant powder, percussion caps and small arms cartridges must be stored separately from one another (for example, on different shelves or separated by a wooden barrier);
(h) the storage unit must be attended when it is unlocked;
(i) the storage unit must be kept clean, dry, organized and free of grit;
(j) any spill, leakage or other contamination in the storage unit must be cleaned up immediately;
(k) precautions that minimize the likelihood of fire in or near the storage unit must be taken; and
(l) a sign that displays the words “Danger — Fire Hazard/Risque d’incendie” in letters at least 10 cm high and that prohibits smoking using letters, or a symbol, at least 10 cm high must be posted on the storage unit in a clearly visible location.
- SOR/2022-121, s. 4
- Date modified: