Canada – Newfoundland and Labrador Offshore Marine Installations and Structures Occupational Health and Safety Transitional Regulations

Version of section 136 from 2015-01-05 to 2017-06-01:

  •  (1) Subject to subsections (2) and (3), the concentration of an airborne chemical agent or combination of chemical agents in a workplace must be less than 50% of the lower explosive limit of the chemical agent or combination of chemical agents.

  • (2) If a source of ignition may ignite the concentration of an airborne chemical agent or combination of chemical agents in a workplace, that concentration must not exceed 10% of the lower explosive limit of the chemical agent or combination of chemical agents.

  • (3) Subsection (1) does not apply if

    • (a) the workplace is in a hazardous location as defined in the Canadian Electrical Code;

    • (b) the workplace is equipped with an alarm system that will automatically be activated when the concentration referred to in subsection (1) exceeds 60% of the lower explosive limit of the chemical agent or combination of chemical agents; and

    • (c) no employee is exposed to a level in excess of 75% of the lower explosive limit of the chemical agent or combination of chemical agents.


Date modified: