Energy Efficiency Regulations, 2016
Marginal note:Energy efficiency standards
660 (1) The energy efficiency standards set out in column 3 of the table to this section apply to walk-in door assemblies described in column 1 that are manufactured on or after June 5, 2017.
Marginal note:Testing standard
(2) A walk-in door assembly complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by the standard set out in column 2 that are applicable to a walk-in door assembly as defined in section 657.
Column 1 Column 2 Column 3 Item Energy-using Product Testing Standard Energy Efficiency Standard 1 Display door assemblies for walk-in coolers 10 C.F.R. Appendix A Edaily ≤ 0.4306 × Add + 0.41 (0.04 × Add+ 0.41) 2 Display door assemblies for walk-in freezers 10 C.F.R. Appendix A Edaily ≤ 1.6146 × Add + 0.29 (0.15 × Add+ 0.29) 3 Freight door assemblies for walk-in coolers 10 C.F.R. Appendix A for Edaily
10 C.F.R. Appendix B for RSI-value (R-value)
Edaily ≤ 0.4306 × And + 1.9 (0.04 × And + 1.9)
RSI-value ≥ 4.40 m²·K/W (25 ft²·°F h/Btu)
4 Freight door assemblies for walk-in freezers 10 C.F.R. Appendix A for Edaily
10 C.F.R. Appendix B for RSI-value (R-value)
Edaily ≤ 1.2917 × And + 5.6 (0.12 × And + 5.6)
RSI-value ≥ 5.64 m²·K/W (32 ft²·°F h/Btu)
5 Passage door assemblies for walk-in coolers 10 C.F.R. Appendix A for Edaily
10 C.F.R. Appendix B for RSI-value (R-value)
Edaily ≤ 0.5382 × And + 1.7 (0.05 × And + 1.7)
RSI-value ≥ 4.40 m²·K/W (25 ft²·°F h/Btu)
6 Passage door assemblies for walk-in freezers 10 C.F.R. Appendix A for Edaily
10 C.F.R. Appendix B for RSI-value (R-value)
Edaily ≤ 1.5069 × And + 4.8 (0.14 × And + 4.8)
RSI-value ≥ 5.64 m²·K/W (32 ft²·°F h/Btu)
- SOR/2018-201, s. 76
- SOR/2022-265, s. 35
- SOR/2022-265, s. 47