SCHEDULE 1(Section 141)
Approach Boundaries for Alternating Current Systems (distance from energized electrical conductor or circuit part to person)
Item | Column 1 | Column 2 | Column 3 | Column 4 |
---|---|---|---|---|
Limited Approach Boundary | ||||
Nominal System Voltage Range, Phase to PhaseFootnote for Approach Boundaries for Alternating Current Systems (distance from energized electrical conductor or circuit part to person)a | Exposed Energized Electrical Conductor | Exposed Energized Circuit Part | Restricted Approach Boundary | |
1 | Less than 30 V | Not applicable | Not applicable | Not applicable |
2 | 31 V – 150 V | 3.0 m | 1.0 m | > 0 m |
3 | 151 V – 750 V | 3.0 m | 1.0 m | 0.3 m |
4 | 751 V – 15 kV | 3.0 m | 1.5 m | 0.7 m |
5 | 15.1 kV – 36 kV | 3.0 m | 1.8 m | 0.8 m |
6 | 36.1 kV – 46 kV | 3.0 m | 2.5 m | 0.8 m |
7 | 46.1 kV – 72.5 kV | 3.0 m | 2.5 m | 1.0 m |
8 | 72.6 kV – 121 kV | 3.3 m | 2.5 m | 1.0 m |
9 | 138 kV – 145 kV | 3.4 m | 3.0 m | 1.2 m |
10 | 161 kV – 169 kV | 3.6 m | 3.6 m | 1.3 m |
11 | 230 kV – 242 kV | 4.0 m | 4.0 m | 1.7 m |
12 | 345 kV – 362 kV | 4.7 m | 4.7 m | 2.8 m |
13 | 500 kV – 550 kV | 5.8 m | 5.8 m | 3.6 m |
14 | 765 kV – 800 kV | 7.2 m | 7.2 m | 4.9 m |
Return to footnote aFor single-phase systems above 250 V, select the range that is equal to the system’s maximum phase-to-ground voltage times 1.732.