Marginal note:Attributed emissions (Eth)
21 The quantity of CO2 emissions attributed to the production of useful thermal energy by a unit during a calendar year is determined by the formula
Hpnet × bEI
where
- Hpnet
- is the net quantity of useful thermal energy, expressed in GJ, determined by the formula
where
- t
- is the tth period, where “t” goes from 1 to x and where x is the total number of periods during which the unit produced useful thermal energy during the calendar year,
- i
- is the ith heat stream exiting the unit, where “i” goes from 1 to n and where n is the total number of heat streams exiting the unit,
- houti
- is the average specific enthalpy of the ith heat stream exiting the unit during period “t”, expressed in GJ/tonne and determined based on the measurement, using a continuous measuring device, of the temperature and pressure of that heat stream,
- Mouti
- is the mass flow of the ith heat stream exiting the unit during period “t”, expressed in tonnes and determined using a continuous measuring device,
- j
- is the jth heat stream, other than condensate return, entering the unit, where “j” goes from 1 to m and where m is the total number of heat streams entering the unit,
- hinj
- is the average specific enthalpy of the jth heat stream, other than condensate return, entering the unit during period “t”, expressed in GJ/tonne and determined based on the measurement, using a continuous measuring device, of the temperature and pressure of that heat stream, and
- Minj
- is the mass flow of the jth heat stream, other than condensate return, entering the unit during period “t”, expressed in tonnes and determined using a continuous measuring device; and
- bEI
- is the emission intensity of a reference boiler, set to 0.0556 tonnes of CO2 emissions per GJ.