PART 2Energy-Using Products (continued)
DIVISION 11Dry-type Transformers (continued)
Marginal note:Energy-using product
704 (1) A dry-type transformer is prescribed as an energy-using product.
Marginal note:Limits
(2) However, a dry-type transformer is not considered to be an energy-using product
(a) for the purposes of sections 4 and 5, if it was manufactured before January 1, 2005; and
(b) for the purpose of section 705, if it has a BIL of more than 150 kV and was manufactured before January 1, 2010.
Marginal note:Energy efficiency standards — manufactured before January 1, 2016
705 (1) In respect of dry-type transformers that were manufactured on or after January 1, 2005 and before January 1, 2016, the energy efficiency standards set out in column 2 of the table to this section apply to dry-type transformers that were manufactured during the periods set out in column 3.
Marginal note:Testing standard
(2) A dry-type transformer complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by the standard referred to in column 1 that are applicable to a dry-type transformer as defined in section 703.
Column 1 Column 2 Column 3 Item Testing Standard Energy Efficiency Standard Period of Manufacture 1 CSA C802.2 CSA C802.2, Table 1 On or after January 1, 2005 and before January 1, 2010 2 CSA C802.2-12 CSA C802.2-12, Table 1 On or after January 1, 2010 and before January 1, 2016
Marginal note:Energy efficiency standard — single-phase and 1.2 kV voltage class
705.1 (1) In respect of dry-type transformers that are single-phase, in the 1.2 kV voltage class and manufactured on or after January 1, 2016, the energy efficiency standards set out in column 2 of Table 1 to this section apply to dry-type transformers that have a kVA rating described in column 1.
Marginal note:Energy efficiency standards — single-phase and voltage class greater than 1.2 kV
(2) In respect of dry-type transformers that are single-phase, in a voltage class greater than 1.2 kV and manufactured on or after January 1, 2016, the energy efficiency standards that are set out in relation to the product’s BIL rating set out in column 2 of Table 2 to this section apply to dry-type transformers that have a kVA rating set out in column 1.
Marginal note:Interpolation
(3) For the purposes of subsections (1) and (2), if the kVA rating of the product falls between the kVA ratings set out in two consecutive items in column 1 of the applicable table to this section, the energy efficiency standard for the product is an interpolation of the corresponding energy efficiency standards set out in column 2.
Marginal note:Testing standard
(4) A dry-type transformer complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by 10 C.F.R. Appendix A that are applicable to a dry-type transformer as defined in section 703.
Column 1 Column 2 Item kVA Rating % Efficiency When Tested at 35% of Nominal Load 1 15.0 97.70 2 25.0 98.00 3 37.5 98.20 4 50.0 98.30 5 75.0 98.50 6 100.0 98.60 7 167.0 98.70 8 250.0 98.80 9 333.0 98.90 Column 1 Column 2 Item kVA Rating % Efficiency When Tested at 50% of Nominal Load 20-45 kV BIL > 45-95 kV BIL > 95-199 kV BIL 1 15.0 98.10 97.86 97.60 2 25.0 98.33 98.12 97.90 3 37.5 98.49 98.30 98.10 4 50.0 98.60 98.42 98.20 5 75.0 98.73 98.57 98.53 6 100.0 98.82 98.67 98.63 7 167.0 98.96 98.83 98.80 8 250.0 99.07 98.95 98.91 9 333.0 99.14 99.03 98.99 10 500.0 99.22 99.12 99.09 11 667.0 99.27 99.18 99.15 12 833.0 99.31 99.23 99.20
Marginal note:Energy efficiency standards — three-phase and 1.2 kV voltage class
705.2 (1) In respect of dry-type transformers that are three-phase, in the 1.2 kV voltage class and manufactured on or after January 1, 2016, the energy efficiency standards set out column 2 of Table 1 to this section apply to dry-type transformers that have a kVA rating set out in column 1.
Marginal note:Energy efficiency standards — three-phase and voltage class greater than 1.2 kV
(2) In respect of dry-type transformers that are three-phase, in a voltage class greater than 1.2 kV and manufactured on or after January 1, 2016, the energy efficiency standards that are set out in relation to the product’s BIL rating set out in column 2 of Table 2 to this section apply to dry-type transformers that have a kVA rating set out in column 1.
Marginal note:Interpolation
(3) For the purposes of subsections (1) and (2), if the kVA rating of the product falls between the kVA ratings set out in two consecutive items in column 1 of the applicable table to this section, the energy efficiency standard for the product is an interpolation of the corresponding energy efficiency standards set out in column 2.
Marginal note:Reduced energy efficiency standard
(4) The energy efficiency standard that is applicable to a dry-type transformer under this section is reduced by 0.11 if the transformer has multiple high-voltage windings and a voltage ratio other than 2:1.
Marginal note:Testing standard
(5) A dry-type transformer complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by 10 C.F.R. Appendix A that are applicable to a dry-type transformer as defined in section 703.
Column 1 Column 2 Item kVA Rating % Efficiency When Tested at 35% of Nominal Load 1 15.0 97.89 2 30.0 98.23 3 45.0 98.40 4 75.0 98.60 5 112.5 98.74 6 150.0 98.83 7 225.0 98.94 8 300.0 99.02 9 500.0 99.14 10 750.0 99.23 11 1 000.0 99.28 Column 1 Column 2 Item kVA Rating % Efficiency When Tested at 50% of Nominal Load 20-45 kV BIL > 45-95 kV BIL > 95-199 kV BIL 1 15.0 97.50 97.18 96.80 2 30.0 97.90 97.63 97.30 3 45.0 98.10 97.86 97.60 4 75.0 98.33 98.13 97.90 5 112.5 98.52 98.36 98.10 6 150.0 98.65 98.51 98.20 7 225.0 98.82 98.69 98.57 8 300.0 98.93 98.81 98.69 9 500.0 99.09 98.99 98.89 10 750.0 99.21 99.12 99.02 11 1 000.0 99.28 99.20 99.11 12 1 500.0 99.37 99.30 99.21 13 2 000.0 99.43 99.36 99.28 14 2 500.0 99.47 99.41 99.33 15 3 000.0 99.47 99.41 99.33 16 3 750.0 99.47 99.41 99.33 17 5 000.0 99.47 99.41 99.33 18 7 500.0 99.48 99.41 99.39