PART 3Vessels of Less than 24 m in Length (continued)

Structural Fire Protection (continued)

Insulation, Fire Retardant Coatings and Fire Retardant Resins (continued)

  •  (1) This section applies in respect of the insulation, fire retardant coating and fire retardant resin required by this Part.

  • (2) The insulation, fire retardant coating or fire retardant resin used on a deck or bulkhead must

    • (a) cover the entire surface of the deck or bulkhead;

    • (b) be carried past the penetration, intersection or terminal point of the deck or bulkhead for a distance of at least 380 mm;

    • (c) be installed on the side on which the fire risk is higher, unless it is not possible to do so; and

    • (d) if the insulation, coating or resin is vulnerable to damage, be protected to prevent any loss of its fire-resistant properties.

  • (3) The insulation installed on a deck or bulkhead must be held in place by closely spaced studs and clips or by another method that will

    • (a) hold the insulation in place for at least 60 minutes when it is exposed to fire; and

    • (b) hold the insulation in place despite the vibration and motion of the vessel and the normal wear.

  • (4) If insulation is installed on the stiffener side of a deck or bulkhead, at least 50% of the thickness of the insulation must be installed on top of the stiffener.

  • (5) Fire retardant coating and fire retardant resin must be applied, and the surfaces to which they are to be applied must be prepared, in accordance with the specifications of its manufacturer.

Cooking and Heating Appliances

  •  (1) On a passenger-carrying vessel, the boundaries of a galley that contains cooking appliances must consist of “F” class divisions or “B-15” class divisions, or be insulated with 30-minute fire rated insulation, if

    • (a) the vessel has sleeping accommodations; or

    • (b) meals are cooked in the galley with an appliance, other than a microwave, that has a heating surface that can exceed 120°C.

  • (2) Every cooking or heating appliance must be installed in accordance with the appliance manufacturer’s recommendations, if any, with regard to clearances and with regard to materials, including insulation, installed in way of the appliance. If the space does not allow the minimum clearance, if any, recommended by the manufacturer,

    • (a) 30-minute fire rated insulation must be installed to the surfaces in way of the appliance;

    • (b) all surfaces around the appliance must be non-combustible; and

    • (c) the appliance must be installed so that the temperature of every surface adjacent to the appliance will not, when the appliance is operated, exceed 90°C or, if the surface is readily accessible, 60°C.

  • (3) If life saving equipment, a muster station or an embarkation station is located on the deck above a space that contains a cooking or heating appliance, or on the other side of a bulkhead delimiting that space,

    • (a) in the case of a steel or aluminum vessel, the deck or bulkhead must consist of “A-15” class divisions in way of the life saving equipment, muster station or embarkation station; and

    • (b) in the case of a wooden or composite vessel, the deck or bulkhead must be insulated with 30-minute fire rated insulation in way of the life saving equipment, muster station or embarkation station.

Wheelhouses, Machinery Spaces and Lockers for Flammable or Combustible Materials

  •  (1) Subject to subsection 320(1), the decks and bulkheads separating a wheelhouse from any other space must

    • (a) consist of “F” class divisions or “B-15” class divisions;

    • (b) be insulated with 30-minute fire rated insulation; or

    • (c) be coated with a fire retardant coating of the intumescent type.

  • (2) Machinery space boundaries must, to the extent feasible, prevent the passage of smoke.

  • (3) Every locker for storing flammable or combustible liquids

    • (a) must be of a construction that retards the propagation of flame on the inside of the locker by means of 30-minute fire rated insulation or fire retardant coating of the intumescent type;

    • (b) must not permit the escape of gas within an enclosed space; and

    • (c) must be vented outside independently of the ventilation from any other space.

Vessels Carrying More than 100 Passengers or More than 12 Berthed Passengers

  •  (1) On a vessel carrying more than 100 passengers or more than 12 berthed passengers, every deck that separates an accommodation space, service space or wheelhouse from an accommodation space, service space or wheelhouse, and every deck or bulkhead in way of life saving equipment, a muster station or an embarkation station, must

    • (a) in the case of a steel or aluminum vessel, consist of “A-15” class divisions; and

    • (b) in the case of a composite vessel, be insulated with 30-minute fire rated insulation.

  • (2) On a vessel carrying more than 12 berthed passengers,

    • (a) the vessel must be divided into fire zones that include berths for a maximum of 12 persons;

    • (b) the decks delimiting the fire zones must consist of “A-15” class divisions or be insulated with 30-minute fire rated insulation; and

    • (c) the bulkheads delimiting the fire zones must consist of “F” class divisions or “B-15” class divisions.

Wooden or Composite Vessels

Machinery Spaces

 On a wooden or composite vessel, the exposed surfaces within a machinery space, including supporting structures and engine seats, must be coated with a final layer of fire retardant coating or fire retardant resin.

  •  (1) On a wooden or composite vessel, every deck or bulkhead that separates a machinery space from an accommodation space, galley, wheelhouse, space containing a fixed gas fire-extinguishing system, or compartment to store gas containers must consist of “F” class divisions or “B-15” class divisions, or be insulated with 30-minute fire rated insulation.

  • (2) On a vessel that is not more than 15 m in length overall, any area of a deck or bulkhead in which the available space or physical configuration makes it impossible to meet the requirements of subsection (1) may instead be coated with fire retardant coating of the intumescent type or with fire retardant resin.

Composite Passenger-carrying Vessels — Laminate for the Hull, Decks and Superstructures

 On a composite passenger-carrying vessel carrying more than 100 passengers or more than 12 berthed passengers or that engages on voyages that are not sheltered waters voyages or near coastal voyages, Class 2, limited,

  • (a) the laminate for the hull, decks and superstructures must not be a sandwich construction; and

  • (b) the resin in the laminate must be a resin that a product certification body or a testing laboratory has certified

    • (i) as having a flame spread rating of 25 or less when tested in accordance with the standard ASTM E84, entitled Standard Test Method for Surface Burning Characteristics of Building Materials, or

    • (ii) as meeting the requirements of Military Specification Resins, Polyester Low Pressure Laminating Fire-Retardant, MIL-R-21607, published by the Naval Sea Systems Command, United States Department of the Navy.

Steel or Aluminum Vessels

  •  (1) On a steel or aluminum vessel, every deck or bulkhead that separates a machinery space from an accommodation space, galley, wheelhouse, space containing fixed gas fire-extinguishing equipment, or compartment to store gas containers must

    • (a) if the vessel is a passenger-carrying vessel, consist of “A-15” class divisions or be insulated with 30-minute fire rated insulation; and

    • (b) if the vessel is not a passenger-carrying vessel, consist of “A-0” class divisions.

  • (2) On a vessel that is not more than 15 m in length overall, any area of a deck or bulkhead in which the available space or physical configuration makes it impossible to meet the requirements of subsection (1) may instead be coated with fire retardant coating of the intumescent type.

Openings in Boundaries, Decks, Bulkheads and Lockers

  •  (1) The fire integrity of the boundaries, decks, bulkheads and lockers referred to in sections 318 to 320, 322 and 324 must not be impaired by the passage of electrical cables, pipes, trunks, ducts or other transit devices through the divisions.

  • (2) The doors and other closures of openings in the boundaries, decks, bulkheads and lockers referred to in sections 318 to 320, 322 and 324 must have fire-resistant properties equivalent to those of the class divisions of the structures in which they are fitted.

Interior Finish and Furniture

  •  (1) Subject to section 327, the exposed surfaces within an accommodation space, service space or wheelhouse must

    • (a) be made of a material that

      • (i) a product certification body, testing laboratory or recognized organization has certified as having a flame spread rating or index of 25 or less and a smoke developed classification or index of 100 or less when tested in accordance with the standard CAN/ULC-S102, entitled Standard Method of Test for Surface Burning Characteristics of Building Materials and Assemblies, published by the Standards Council of Canada, or the standard ASTM E84, entitled Standard Test Method for Surface Burning Characteristics of Building Materials, or

      • (ii) meets the flame spread, smoke and toxicity requirements set out in Annex 1 to the FTP Code; or

    • (b) be coated with fire retardant coating or fire retardant resin.

  • (2) Paint, varnish or similar preparation that contains a nitro-cellulose base must not be applied, and a fabric that contains nitro-cellulose must not be fitted, to any interior surface of the vessel or any furniture.

 